Cabinet + Vision 6Kva module
More info
" Cabinet + module Vision 6Kva "
Cabinet
Cabinet with an inverter module MOD Vision of 6kva rackmount 19 ". Possibility of increasing the power adding up to 5 modules rack (6kva or 10Kva).
Features
- Input power factor up to 0.99
- On-line„Double conversion“ technology (VFI)
- Internal static and manual bypass in each module (no centralized bypass required)
- Hot swappable power and battery modules Wide input voltage range 208-478VAC
- Adjustable battery voltage (192-240VDC, 16-20 batteries)
- Only one battery string for N+1 application 6A charging current per module
- Adjustable charging current
- Automatic load sharing
- Diesel-genset compatibility
- Big touchscreen LCD-display
- Various monitoring systems
- High overload capacity
- Low noise
- RS232/RS485 Interface Relay card (dry contacts)
- EPO (Emergency Power Off )
- 1 year warranty (electronics)
Vision MOD online 6Kva inverter
On line type (also called double conversion )
This UPS operates a double conversion
- In normal mode, the UPS inverter is placed between the network and the load. The power supplied to the consumers goes constantly through the UPS which carries a double conversion AC / DC and DC / AC .
- In standalone mode , the battery supplies power to the inverter and the inverter supplies power to the load. This configuration is the most expensive but also the most comprehensive in terms of the protection of the load. The inverter converts continuously the voltage of the grid, allowing precise control of the voltage and frequency of the output . Given the isolation of consumers over the electric grid, power system disturbances are eliminated at the UPS output
Furthermore, the transition from normal mode to autonomous mode is instant without any swapping delay . The UPS directs the load to the network using a static bypass contactor in caseof a failure or battery discharge. The UPS is synchronized with the grid, the transfer is carried out without break. This UPS is the best protection against interference and micro-breaks for sensitive equipment.
Performance and productivity
- Technology supply on-line double conversion, constantly regulates voltage and frequency.
- Up to 98% efficiency in economy mode.
- Continuously, the inverter outputs a sinusoidal current "clean" to the connected equipment.
Flexibility
- Its graphical display provides clear and detailed information on the UPS status
- Its can measure power consumption and display via the LCD screen.
- To double the power, he can be connected in parallel with another UPS Vision MOD 6kva.
Specifications
Input | |
Nominal capacity | 6kva / 4,8kW |
Rated voltage | 380/400VAC or 220/230VAC |
Voltage range | 208-478VAC (3/1) or 120-276VAC (1/1) |
Frequency | 40-70Hz |
Input power factor | >0,99 |
Current THDi | <5% |
Output | |
Voltage | 220/230VAC +- 2% with pure sine wave |
Frequency | 50/60Hz |
Harmonic distortion | <2% (linar load) / <5% (non-linear load) |
Crest factor | 3:1 |
Efficiency | ECO-mode >98% / Normal-mode > 90% |
Battery | |
Type | VRLA |
Voltage | Optional battery quantity: 192/216/240V (16-20 batteries) |
Maximum charging current | 6A per module (can be set according to battery capacity installed) |
Additional backup time | Internal batteries for short backup time or external battery cabinet for long backup |
Protection | |
Input / Output | Overload, Overheating, Short Circuit, Battery Low, Noise and Spike Suppression |
Overload AC-Mode | ?110% - 60min / ?125% - 10min / ?150% - 1min |
Overload Battery Mode | ?110% - 30sec / ?125% - 1sec / ?150% - 200msec |
Overload Bypass Mode | Input Breaker 60A |
Alarms - Indication | |
Audible alarm | Beeping sound for Line Failure, Battery Low, Bypass - Overload Status, Fault Status |
LED-Alarm | Line - Backup - Eco Mode, Bypass, Battery Low/Bad/Disconnect, Overload, Fault |
LCD-Display | Big touchscreen display 5" |
Bypass | |
Type | Internal static (automatic) and manual bypass / External bypass optional |
Bypass voltage range | Max.voltage: +15%(optional +5/10/25% ) / Min. voltage: -45% (optional -20/30%) Frequency protection range: ±10% |
Standards | |
Certificates | CE, EN62040-1-1 (ESD), EN62040-2 (EMI) |
Protection class | IP20 |
Environment | |
Temperature | Working temperature: 0 - 40°C / Storage temperature: -25 - 55°C |
Humidity / Altitude | 0-95% non condensing / < 1500m |
Audible noise at 1m | <50dB /1m according to EN62040-2 |
Interface | |
In the cabinet | RS232 / RS485 / 2 free slots / dry contacts / EPO - software included |
In the module | RS232 |
Optional | SNMP-Adapter |
Dimensions of the module | |
Dimensions WxDxH | 443x580x131mm (3u) |
Weight | 25kg (without batteries 13,5kg) |
Optional
- 2X Vision MOD online 6Kva Inverter
- 2X Vision MOD online 10Kva Inverter