Hybrid Inverter BatterX BAT30X
More info
" Hybrid inverter batterX : the solar intelligence "
The energy supply
- Hybrid function with scalable OFF Grid MPPT controller
- UPS, ON-Line "double conversion" technology (VFI)
- Controllable input current management
- Split / double bypass input
- Output power factor 0.9
- Up to 8 units in parallel
- High efficiency > 94%
- Backfeed protection
The brain :
- Energy storage with batteries "Made in Germany"
- UPS (Uninterruptible Power Supply) / Voltage Frequency independent
- Controllable energy-mix of different energy sources
- Free choice of energy supplier (100% green electricity)
- Cost reduction by peak load elimination
- Future-proof thanks to
- Open source
- Community
- Apps
- Add-ons
- Plug-ins
- Updates and upgrades ...
- Up to 18 programmable interfaces IN/OUT
- Remote diagnosis and Remote Monitoring
Power
Highest output range : 10kVA to 4MVA
Battery storage : 5kWh to > 1MWh
Operating
Solar energy
In combination with a PV installation the solar energy is the primary energy source to supply the load with stable and uninterruptible power. It also charges your batteries.
Grid & generator supply
The grid only supplies the load when the solar and/or battery energy is not strong or not available. Partial grid supply is managed by the Energy Flow Manager (EFM)
Battery storage
With this unique and modular technology, it is able to provide very big storage capacities. In combination with solar energy, it can power and protect you during many hours or days.
BatterX | BAT 10X | BAT 15X | BAT 20X | BAT 30X | BAT 40X | BAT 60X | BAT 80X | BAT 100X | BAT 120X | BAT 160X | BAT 200X | BAT 250X | BAT 300X | BAT 400/500X |
Power (kVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 120 | 160 | 200 | 250 | 300 | 400/500 |
Input | ||||||||||||||
Voltage | 380/400/415Vac 3 phase +N, +/-20% (415Vac +15% - 25%) | |||||||||||||
Frequency range | 50/60Hz selectable, +/- 10Hz | |||||||||||||
Power factor | 0.99 | |||||||||||||
Harmonic distortion (THDI) | <3% | |||||||||||||
Additional bypass input | Yes | |||||||||||||
Bypass voltage range | 380/400/415 Vac 3 phase +N, +/-10% | |||||||||||||
Solar charge controller | Yes - hybrid function | |||||||||||||
Output | ||||||||||||||
Power factor | 0.9 | |||||||||||||
Power (kVA) | 9 | 13.5 | 18 | 27 | 36 | 54 | 72 | 90 | 108 | 144 | 180 | 225 | 270 | 360/400 |
Voltage regulation | 380/400/415 Vac 3 phase +N, +/-1% (220/230/240 Vac for 10-30kVA) | |||||||||||||
Frequency | 50/60Hz adjustable | |||||||||||||
Frequency regulation | Line synchronizedu +/- 2% battery mode +/-0.1% adjustable | |||||||||||||
Efficiency | Up to 94% | |||||||||||||
Crest factor | 3:1 | |||||||||||||
Overload protection | 100-125% 10 min, 125-150% 60 sec | |||||||||||||
Additional protection | Short-circuit, voltage and current range | |||||||||||||
Harmonic distortion (THD) | <3% à 100% linear load | |||||||||||||
Battery | ||||||||||||||
Type | VRLA AGM/GEL or other types | |||||||||||||
Nominal voltage | +/- 360Vdc (2x30-12Vdc) | |||||||||||||
Float or end of discharge DC voltage | +/- 405Vdc, +/- 300Vdc | |||||||||||||
Battery | Internal | Externam | ||||||||||||
Protection | Overcharging, battery duses, temperature compensation | |||||||||||||
Automatic test | Daily, weekly (adjustable) | |||||||||||||
Hybrid Off Grid Controller | ||||||||||||||
Power | 10 and 40kW (up to 8 units in parallel) | |||||||||||||
MPPT input | 260-640Vdc (40kW TBA) | |||||||||||||
Input min/max Voc | 200Vdc / 800Vdc (40kW TBA) | |||||||||||||
Efficiency | ≥97% | |||||||||||||
Communication | RS232, 4 dry contacts, EPO, multi language graphical LCD | |||||||||||||
Dimensions H x D x W / weight | 10kW : 3Ux500x440mm / 17kg (40kW TBA) | |||||||||||||
General | ||||||||||||||
Standard & certificates | EMC/LVD/EMI - EN62040-1/2, EN60950, CE | |||||||||||||
UPS interface | Multi language graphical LCD | |||||||||||||
Communication ports - UPS | 2x RS232 ports, 4 dry contact (in option 8 dry contacts) | |||||||||||||
Communication ports - Raspberry PI | 4 USB, HDMI, Ethernet, Micro SD card | |||||||||||||
Communication ports - Controller card | 18 programmables IN/OUT interfaces, RS232, RS485 | |||||||||||||
Input | Generator contact and emergency power off | |||||||||||||
Genset kit | User programmable | |||||||||||||
Software | Management software | |||||||||||||
Alarm | 200 events (time and date) / in option 500 events | |||||||||||||
Protection | Over-temperature, over-current, over-temperature alarm | |||||||||||||
Temperature range | 0°C - 40°C | |||||||||||||
Protection degree | IP20 (IP54 in option) | |||||||||||||
Humidity / altitude | 90% max without condensation / < 1000m | |||||||||||||
Audible noise at 1m | ≤ 56dB | ≤ 61dB | ≤ 64dB | ≤ 67dB | ≤ 72dB | |||||||||
Weight (kg) | 86 | 86 | 92 | 98 | 175 | 182 | 196 | 218 | 218 | 259 | 480 | 560 | 650 | 770 |
Dimensions (mm) H x W x D | 1037 x 398 x 812 | 1437 x 513 x 852 | 1797 x 882 x 763 | 1797 x 1246 x 763 |