Product or component type | Circuit breaker |
Device short name | C60N |
Poles description | 2P |
Number of protected poles | 2 |
[In] rated current | 40A |
Network type | AC DC |
Trip unit technology | Thermal-magnetic |
Curve code | C |
Breaking capacity | Icn 3000 A à 230 V CA 50/60 Hzconforming to EN/IEC 60898-1 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Network frequency | 50/60 Hz |
[Ue] rated operational voltage | 230 V CA 50/60 Hz |
Magnetic tripping limit | 5...10 x In |
[Ics] rated service breaking capacity | 3.75 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz 2.25 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz 6 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz |
Limitation class | 3 conforming to EN/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
Contact position indicator | Yes |
Control type | Toggle |
Local signalling | ON/OFF indication |
Mounting mode | Clip-on |
Mounting support | 35 mm symmetrical DIN rail |
Comb busbar distribution block compatibility | NO |
9 mm pitches | 4 |
Height | 81 mm |
Width | 36 mm |
Depth | 73 mm |
Product weight | 0.238 kg |
Mechanical durability | 10000 cycles |
Connections - terminals | Tunnel type terminals rigid wire(s) 25 mm² max Tunnel type terminals flexible wire(s) 16 mm² max |
Tightening torque | 3.5 N.m |
Earth-leakage protection | Separate block |
Product compatibility | C60 accessories C60 auxiliary |
Standards | EN 60898 EN/IEC 60947-2 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % 55 °C |
Operating altitude | 2000 m |
Ambient air temperature for operation | -25...60 °C |
Ambient air temperature for storage | -40...80 °C |
- Number of Reviews : 1
- Average Grade : 5 /5
- C. Olivier
- the 17/07/2020
5/5
Specifications
Disjoncteur |